ERC 211
Description
Specifications
Functionality & Interfaces
-
Outputs:
-
Single high‑capacity relay (DO1) for compressor/valve control or simple heating element (16 A at 230 VAC, 10 FLA/60 LRA; 16 FLA/72 LRA at 115 VAC)
-
-
Inputs:
-
One analogue temperature sensor input (Sair)
-
One flexible input, either analogue or digital (e.g. condenser sensor or door alarm, configurable via software)
-
User Interface
-
Four push-buttons and a red-display panel
-
Easy menu navigation with preconfigured application profiles for refrigerating or heating environments
Applications & Pre‑configured Modes
-
Configurable apps:
-
Cooling with timed or sensor-terminated defrost, medium temperature (2 – 6 °C)
-
Heating thermostat (20 – 60 °C)
-
And other presets for typical commercial refrigeration setups
-
Protection & Safety Features
-
Compressor protection via anti‑cycle timers
-
Voltage protection and zero‑cross relay switching to extend relay life and reduce electrical stress
-
Thermal and high‑pressure condensing protection logic embedded in firmware
Sensors & Compatibility
-
Supports NTC (5 K / 10 K), PTC, or Pt1000 sensor types—must use the same type for all inputs
Physical & Electrical Specifications
-
Supply voltage: 197–250 VAC (50/60 Hz) for 230 V models
-
Weight/Size: ~0.15–0.24 kg; compact DIN-module or clip mounting (footprint approx. 83×66×48 mm)
Approvals & Standards
-
UL 60730, EN 60730, ENEC, CE LVD & EMC, EAC, NSF, cURus certified
-
Complies with HACCP temperature monitoring (EN 13485 Class I) when paired with recommended sensors such as AKS 12